๐ โน499 ์ด์ ๋ฌด๋ฃ ๋ฐฐ์ก ยท ๐ต ์ธ๋ ์ ์ญ ์ฐฉ๋ถ ๊ฒฐ์
Repair guide ยท VFD / AC drive ยท 5 min
The large electrolytic capacitors on a drive's DC bus age with heat and running hours. Worn capacitors cause random trips, overheating and finally damage to the rectifier and IGBTs, so replacing them in time protects the whole drive.
โ ๏ธ Safety first: these checks are for trained electricians and maintenance engineers. Work only on isolated equipment, use a meter rated CAT III, and never open a powered unit. If in doubt, send photos to us instead.
You need: Multimeter (DC voltage) ยท ESR / capacitance meter for a workshop check
Switch off and isolate the supply, then wait at least 10 minutes and measure the DC bus (P/+ and N/โ) with a multimeter on the DC 1000 V range before touching anything. Drive and SMPS capacitors can hold a lethal charge long after the display goes off. Then check the capacitor tops and sleeves for bulging, cracks or electrolyte.
A dead fan or blocked heatsink makes the capacitors age much faster. Clean filters and replace failed fans.
On a running drive (from the keypad monitor if available), the DC bus should be steady at about 1.35 ร the mains voltage (around 540 V for 400 V supply). Large dips under load point to weak capacitors or a rectifier problem.
Before running a drive that was stored unpowered for a long time, its capacitors usually need reforming (slowly raised voltage). Check the manual โ switching it straight on can damage it.