Repair guide · VFD / AC drive · 7 min
Overcurrent faults (oc, OC, OC1, F0001, E.OC1, OCF and similar) mean the drive measured more current than it allows. The cause can be the load, the motor or cable – or the drive's own power stage. A few checks tell you which.
⚠️ Safety first: these checks are for trained electricians and maintenance engineers. Work only on isolated equipment, use a meter rated CAT III, and never open a powered unit. If in doubt, send photos to us instead.
You need: Multimeter with diode test · Insulation tester (megger) 500 V · Drive manual for the fault code
At start, during acceleration, at constant speed or when stopping – this points to the cause. Look up the code in our fault-code guide for your drive brand.
Increase the acceleration time, check the motor rating data in the parameters, and make sure the machine turns freely by hand.
Isolate the supply, wait for the DC bus to discharge, disconnect U/V/W and run the drive without the motor. If it still trips with OC, the drive's power stage or current sensing is faulty.
With the drive disconnected, test motor windings and cable to earth at 500 V. Low insulation (below about 1 MΩ) means the motor or cable is the problem – never megger with the drive connected.
Switch off and isolate the supply, then wait at least 10 minutes and measure the DC bus (P/+ and N/–) with a multimeter on the DC 1000 V range before touching anything. Drive and SMPS capacitors can hold a lethal charge long after the display goes off. Then use the diode test from P/+ and N/– to U, V and W. A short or very low reading in any direction means a failed IGBT module.