Repair guide ┬╖ Inverter / UPS card ┬╖ 5 min
When an inverter or UPS stops charging or gives no backup, the battery is the first suspect тАУ but mains sensing, charging MOSFETs and relays on the control card fail too. Simple voltage checks separate battery problems from card faults.
тЪая╕П Safety first: these checks are for trained electricians and maintenance engineers. Work only on isolated equipment, use a meter rated CAT III, and never open a powered unit. If in doubt, send photos to us instead.
You need: Multimeter (DC voltage) ┬╖ Hydrometer for tubular batteries
Measure the battery voltage with the inverter off: a 12 V battery should read around 12.6тАУ12.8 V when charged. Clean and tighten the terminals and check the electrolyte level.
With mains on, measure at the battery terminals. In bulk charging it should rise to about 13.8тАУ14.4 V per 12 V battery. No rise means the charging section is not working.
Switch off heavy loads (heaters, motors). Beeping on overload often goes away when the load is within the rating.
With the unit switched off and disconnected from mains and battery, check the internal fuses. A blown battery fuse usually means a shorted MOSFET bank.